You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 9 Next »


EIO in the target cave: related documents 


Microwave motor control system 

Motor controller ORC: Microwave motor Control Box.pdf


Operating the microwave system Polarization  

Turning on the system 

  • Turn on the microwave chiller near the NM3 area
  • Turn on the microwave interlock box in the slow controls rack. After about one minute, the value displayed on the “Gem sensor “of the interlock box should be greater than 0.10r.
    • If not, do not proceed and contact the target expert.
















  • Turn on the “Varian” power supply in the slow controls rack.
    • Initially, the power supply will on the “Filament delay” state for about 2 minutes
    • After two minutes the power supply will be changed the state to “Standby”. Now the power supply is ready.
    • If the power supply goes to the “Summary fault” state, contact the target expert
  • Change the power supply mode from Local to Remort by pressing the button as in the picture below

 

  • Turn on the EIP frequency counter in the slow controls rack and press 7 3 7 numeric buttons. This will select the correct frequency band
  • Turn the power supply controller in the control room rack and set the mode to Local. Make sure the power supply is in the Standby mode

  • Now the power supply is ready to transmit the microwave to the target cups.


The microwave VI automatically controls the motor position to maintain the EIP frequency at 140.18 GHz. Make sure the "Track EIP" is on.

           

  • Restoring the microwave system from fault conditions 

Whenever there is a loss of microwave frequency, you will hear a continuous warning sound from the microwave computer.

You will see a blinking "Lost EIP signal!!!" warning on the microwave VI as in the image below

There are three instances where you can hear this warning

    • Case 1 : "Lost EIP signal!!!" on the VI. But EIP on the camera shows frequency numbers

     Action needed: Stop the VI by pressing "Stop VI". Restart the VI by pressing the "Run" button

    • Case 2: "Lost EIP signal!!!" on the VI.  EIP on the camera is not showing frequency numbers. There is no fault warning on the microwave power supply in the control room rack.

Action needed: Slightly change the motor position until you see the EIP signal

              • Enter 1 degree in the VI and press the right arrow to move the motor by 1 degree. Keep pressing until you see a signal. If it is not showing anything after 5 presses, change the value to 5 degrees and repeat.  If it is not successful, enter 10 degrees and try.  

    • Case 3: "Lost EIP signal!!!" on the VI.  EIP on the camera is not showing frequency numbers. The microwave power supply in the control room rack is in a faulty condition. 

Action needed:

              1. Reset the power supply fault state 
                • Press the left button to switch to standby mode. Press it again to Transmit. This will reset the fault.  

If not, try following 

                • Press the left button to switch to standby mode. Press the right button two times (The ode will change from Local → Remort→ Local). Press the left button to switch to Transmit

If not, try following 

                • Powercycle the microwave power supply in the slow controls rack using the red toggle switch and Change the mode to Remort. Change the mode to Remort.  Press the left button to switch to Transmit

2. Now you will see frequency numbers on the EIP. If not slightly change the motor position until you see the EIP signal (As in the Case 2 action)



  • No labels