Watch the temperature of the target cups on Strip Charts. The target parameters are Insert# 7 and Insert#8, and the Target parameters are Annealing A and Annealing B. Please use the following strip chart to watch the Target Parameters:
Target-Parameter Multi Monitor (fnal.gov)
https://e906-gat1.fnal.gov/data-summary/e1039/target-par-preset/target-shift-20240430.php
...
- F:NM4LCWFLOW, it should be above 50 GPM (Gallon Per Minute)
- F:NM4LCWT1, it should be less than 100 F
- F:NM4LCWT2, it should be less than 100 F
- F:NM4LCWP1, it should be above 45 psi
- F:NM4LCWP3, it should be above 60 psi
Note: If you are not able to resolve the above problems, then immediately call Target Expert. Please note the contact number of the Target Expert from the Control Room Whiteboard.