Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
  1. Ensure the "AUTO" control of the GV-Bypass PID is OFF.
  2. Check the Present Position on the VI. If it is already closer to 100% and also whether the limit switch for OPEN is GREEN. If not, then fully open the GV-Bypass (wait until you can see the limit switch for OPEN is GREEN).
    The following is an example screenshot when the GV-Bypass is fully opened
    Image

  3. Wait until the pressure is stabilized (here you have to coordinate with the Target Expert to find which pressure you will need it to be stabilized).
  4. Open GV (Gate Valve), and wait until the fridge pressure is stabilized.


  5. Fully close the GV-Bypass valve.
  6. Turn ON the boosters of the roots-stack (from bottom to top ).
  7. Crack open the RUN valve by 0.54 turns.
  8. Turn ON the microwave following Microwave Operation.