You can make various viewpoints of the full system strip charts using this page: https://e906-gat1.fnal.gov/data-summary/e1039

LCW

Two target sub-systems use LCW (Low Conductivity Water) for cooling.
1. Helium Liquefier System (UVA-QT): see QT System Manual for more details.
2. Roots pump-system: see Pumps System Manual for more details.

If you are on the cryo-platform, take the stairs (towards the lower level) and stop mid-way when you see these gauges towards the east wall of the hall.
You will see labels ”LCW Supply” and “LCW Return” on those two separate piping.

Image Added
Both “LCW Supply” and “LCW Return” have a pressure gauge and a temperature gauge. 

The nominal values (as of 01/06/2024):

ParameterAvg. Value
Inlet Pressure ~ 65 psig
Outlet Pressure~  48 psig
Inlet Temperature~ 79 Fahrenheit
Outlet Temperature~ 89 Fahrenheit

Image Added


The nominal values for the outlet LCW temperatures from the QT coldhead compressors should be below 100 Fahrenheit (see the image below)
If you notice this increase above 105 Fahrenheit, then the coldhead compressors will be tripped soon.
Image Added