Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

  1. The volume of an outside gHe tank: 1600 cubic feet
  2. 100 slm rate on Magnet FC is equivalent to ~ 192 LHe liters per day (i.e. assuming both LQ A and B are running)
  3. QT recommendation to keep system minimally pressurized: ~20 psi
  4. Running from 40 psi down to 20 psi would produce about 80 liquid litters and we should be able to do that in about 10 hours (assuming both LQ A and B are running).
  5. Putting a 2200 psi gas bottle into the system will produce 8 liquid liters per bottle.
  6. HR3.docx


The following page contains information on the production and transfer efficiency studies

LHe Production Information
LHe Transfer Efficiency

...